Previous | Contents | Index |
The following messages are logged by one or more of the Protocol Emulators (PEs).
Unsolicited message received. ID !OW out of range.
Current limit
is !OW.
Explanation: Error. An unsolicited message was
received from a PLC, but the unsolicited ID (PLC-2 address) was too
large for the DAS. By default, the largest value for the unsolicited ID
is 127 (decimal). This value can be increased by creating and setting
the parameter ILAN$ABX_MAX_UNSOL_ID. The name of the parameter is
different for each PLC family.
User Action: Create and set the ILAN$ABX_MAX_UNSOL_ID
parameter to be larger than the unsolicited ID received or change the
PLC logic to use a different PLC-2 address. The device must be disabled
and then reenabled to use the parameter.
Unsolicited message received. No matching phypoint found for ID !OW.
Explanation: Error. An unsolicited message was
received from the PLC, but a physical point with a matching unsolicited
ID was not found for this device.
User Action: Create a physical point with a matching
ID and format for the data received from the PLC, or change the PLC
logic to send an unsolicited message with the unsolicited ID and format
of an existing physical point.
Phypoint unsolicited ID !OW - out of range.
Current limit is !OW.
Explanation: Error. A phypoint has been created, but
the unsolicited ID (PLC-2 address) was too large for the DAS. By
default, the largest value for the unsolicited ID is 127 (decimal).
This value can be increased by creating and setting the parameter
ILAN$ABX_MAX_UNSOL_ID. The name of the parameter is different for each
PLC family. If the device is disabled when the phypoint is created,
this message is logged when the device is enabled.
User Action: Create and set the ILAN$ABX_MAX_UNSOL_ID
parameter to be larger than the unsolicited ID used or change the
physical point to use a different PLC-2 address for the unsolicited ID.
The device must be disabled and then reenabled to use the new parameter.
Phypoint unsolicited ID !OW - already defined.
Explanation: Error. A phypoint has been created, but
the unsolicited ID (PLC-2 address) is already in use by another
phypoint. Unsolicited IDs must be unique for this DAS.
User Action: Create the phypoint using a different
unsolicited ID (PLC-2 address).
Attempt to download !AD file to !AD.
Explanation: Error. An attempt was made to download a
file that was uploaded from a PLC with a different processor type. Only
files with the same processor type as the PLC being downloaded to can
be downloaded.
User Action: Download a file with a processor type
that matches the type of the PLC being downloaded to.
PLC memory too small to fit the requested file.
PLC logic file
memory = !UL, PLC memory = !UL.
Explanation: Error. The size of memory in the file
being downloaded is greater than the size of memory in the PLC being
downloaded to.
User Action: Download a file with a memory image that
is less than or equal to the actual size of the memory in the PLC.
Requested download file is not a valid PLC logic file.
Explanation: Error. The file was missing header
information that identified the file as a valid PLC logic file.
User Action: Download a file that is valid to be
downloaded to this PLC.
Data table size mismatch, file = !UW, PLC = !UW.
Explanation: Error. When attempting to download to a
PLC-2 where the interface module is a 1771-KA revision A or 1771-KG
revision A, the data table sizes did not equal each other.
User Action: Download a compatible PLC-2 file to the
PLC-2.
Requested download !AD file, processor type mismatch.
Explanation: Error. An attempt was made to download a
file that was uploaded from a PLC-5 with a different processor type and
the OVERRIDE qualifier was not specified.
User Action: Download a file with a processor type
that matches the type of the PLC being downloaded to or use the
OVERRIDE qualifer to download a compatible PLC logic file.
Downloading !AD file to !AD.
Explanation: Informational. A file with a different
processor type is being downloaded to a PLC-5 processor.
User Action: None.
Index | Contents |