BASEstartm Open DAS
for Allen-Bradley Data Highwaytm
on OpenVMStm
Installation and User's Guide


Previous Contents Index

Figure 3-13 shows the structure of a legal Timer, Counter, Control, SFC Status, Block-Transfer Control, Token Data, ASCII String, PID Control or Message Control data table address for the PLC-5.

Figure 3-14 shows a PLC-5 Timer structure.
Figure 3-15 shows a PLC-5 Counter structure.
Figure 3-16 shows a PLC-5 Control structure.
Figure 3-17 shows a PLC-5 SFC Status structure.
Figure 3-18 shows a PLC-5 Block-Transfer Control structure.
Figure 3-19 shows a PLC-5 Token Data structure.
Figure 3-20 shows a PLC-5 ASCII String structure.
Figure 3-21 shows a PLC-5 PID Control structure.
Figure 3-22 shows a PLC-5 Message Control structure.

Table 3-16 shows examples of legal Timer, Counter, Control, SFC Status, Block-Transfer Control, Token Data, ASCII String, PID Control and Message Control data table addresses for the PLC-5.

Figure 3-13 PLC-5 Timer, Counter, Control, SFC Status, Block-Transfer Control, Token Data, ASCII String, PID Control and Message Control Data Table Address Format


Figure 3-14 PLC-5 Timer Structure


Figure 3-15 PLC-5 Counter Structure


Figure 3-16 PLC-5 Control Structure


Figure 3-17 PLC-5 SFC Status Structure


Figure 3-18 PLC-5 Block-Transfer Control Structure


Figure 3-19 PLC-5 Token Data Structure


Figure 3-20 PLC-5 ASCII String Structure


Figure 3-21 PLC-5 PID Control Structure


Figure 3-22 PLC-5 Message Control Structure


Table 3-16 Example PLC-5 Timer, Counter, Control, SFC Status, Block-Transfer Control, Token Data, ASCII String, PID Control and Message Control Data Table Address Formats
Example Address MMS Type1 Description
$T20:0.ACC UNSIGNED_16 Timer 0 in file 20 accumulated value
C91:3.PRE INTEGER_16 Counter 91 in file 3 preset value
T:20.CTL/15 BIT_STRING Timer 20 in the default timer file (4) Enable bit 2
R6:0.UL BIT_STRING Control 0 in file 6 Unload bit 2
T4:20.TD BIT_STRING Timer 20 in file 4 Timer Done bit 2
R:1.LEN INTEGER_16 Control 1 in the default control file (6) Length value
SC10:0.TIM INTEGER_16 SFC status 0 in file 10 Active Time value
BT11:3.RGS UNSIGNED_16 Block Transfer Control 3 in file 11 Rack/Group/Slot
TD15:2.HI INTEGER_16 Token Data 2 in file 15 High Word value
ST16:0.LEN INTEGER_16 String 0 in file 16 Length value
ST16:2 VISIBLE_STRING 3 String 2 in file 16
ST16:3 OCTET_STRING 3 String 3 in file 16
PD17:2.DVDB FLOAT PID Control 2 in file 17 Deviation Alarm Dead Band
PD17:2.EN BIT_STRING PID Control 2 in file 17 Enable
PD17:1.ADDR[0] INTEGER_16 PID Control 1 in file 17 Master-to-slave address 0
MG18:3.RLEN INTEGER_16 Message Control 3 in file 18 Requested Length
T:5 Structure 4
UNSIGNED_16
UNSIGNED_32
UNSIGNED_32
All of timer 5 in file 4
Control
Preset value
Accumulated value
R8:10 Structure 4
UNSIGNED_16
INTEGER_16
INTEGER_16
All of control 10 in file 8
Control
Length
Position
SC9:5 Structure 4
INTEGER_16
UNSIGNED_16
UNSIGNED_16
All of SFC status 5 in file 9
Control
Preset value
Active Time
BT11:2 Structure 4
UNSIGNED_16
INTEGER_16
INTEGER_16
INTEGER_16
INTEGER_16
UNSIGNED_16
All of BT 2 in file 11
Control
Requested word count
Transmitted word count
File-type number
Word number
Rack/Group/Slot
TD15:2 Structure 4
UNSIGNED_16
UNSIGNED_16
All of Token Data 2 in file 15
High Word
Low Word
PD17:0 Structure 4
UNSIGNED_32
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
Array of 4
UNSIGNED_16
Array of 14
FLOAT
All of PID Control 0 in file 17
Control
Set point
Proportional gain
Initial gain
Derivative gain
Output bias %
Maximum scaled value
Minimum scaled value
Dead band
Set output %
Maximum output limit
Minimum output limit
Update time
Process variable
Error:scaled
Output
PV alarm high
PV alarm low
Deviation alarm +
Deviation alarm -
PV alarm dead band
Deviation alarm dead band
Maximum input
Minimum intput
Tieback %

Master-to-slave address

Reserved/internal use
MG18:2 Structure 4
UNSIGNED_16
INTEGER_16
INTEGER_16
INTEGER_16
Array of 52
INTEGER_16
All of Message Control 2 in file 18
Control
Error code
Requested length
Done length

Reserved/internal use


1Arrays are not supported for structures other than ASCII strings.
2Control bits should be treated as read only and modified only under PLC program control. Modifying these bits from a computer can give unpredictable results.
3Only Varying length strings are supported.
4Write operations are not allowed to structures other than to ASCII strings.


Previous Next Contents Index