3.2.1 Start and Stop

The start and stop functions change the operating mode of a device. The start function enables outputs and the stop function disables outputs. These functions are not supported for the PLC-2 family of devices.

Warning

Devices can control complex and perhaps dangerous industrial processes. Do not use the start and stop functions until you take the required safety precautions and required operating restrictions are put into effect. Refer to the manufacturer's documentation for specific safety precautions.

3.2.1.1 PLC-1774

The start function enables outputs and scanning on the PLC-1774 device. Using the STOP command when the keyswitch position is RUN/PROGRAM LOAD - RUN causes the status of the device to appear as Remote Test. A subsequent START command enables outputs.

Table 3-2 displays the keyswitch positions, current mode, request types, DAS activity, and resulting mode for the PLC-1774 while performing the start and stop functions.

Table 3-2 Start and Stop Function
Keyswitch Position Current Mode Function DAS Activity Resulting Mode
PROGRAM LOAD Program load Start Invalid mode Program load
  Program load Stop None Program load
TEST MONITOR Test mode Start Invalid mode Test
  Test mode Stop None Test
RUN MONITOR Run mode Start Enable outputs Run
  Run mode Stop Disable outputs Run
RUN/PROGRAM LOAD - RUN Remote run Start Enable scanning,Enable outputs Remote run
  Remote run Stop Disable outputs Remote test
RUN/PROGRAM LOAD - TEST Remote test Start Enable scanning Remote test
  Remote test Stop None Remote test
RUN/PROGRAM LOAD - PROG Remote prog Start Invalid mode Remote prog
  Remote prog Stop None Remote prog

Note

PLC-1774 outputs are disabled with a STOP command, but scanning is not stopped.

3.2.1.2 PLC-3

The start function changes the current mode to Run. The stop function changes the current mode to Program Load.

3.2.1.3 PLC-5

The Start function changes the device operating mode to Remote Run. The Stop function changes the device operating mode to Remote Program. The device keyswitch must be in the REM position for the start or stop request to change the device's operating mode.

3.2.1.4 SLC

Start and Stop functions are not supported for SLC processores.