3.2.2 Upload and Download

The upload function transfers the contents of a device's memory to an OpenVMS file. You can specify the STOP qualifier when using the UPLOAD command. If you specify the STOP qualifier, the PE prevents the contents of PLC memory from being modified during the upload. All BASEstar Classic device connection management write functions are rejected with a device busy message.

The download function transfers the contents of an OpenVMS file to a device's memory. You can specify the STOP and RESTART qualifiers to control the device mode when using the DOWNLOAD command. The PE does not allow the operating status of a PLC to be changed unless specified in the DOWNLOAD command.

You must specify the STOP qualifier when you download a running device. The STOP qualifier is a safety mechanism. You must specify the RESTART qualifier to start the device when the download is completed. All device connection management read (except read status) and write functions are rejected with a device busy message during the download.

3.2.2.1 PLC-1774

When you perform the upload function, the keyswitch must be in the RUN-MONITOR, RUN/PROGRAM LOAD, or TEST-MONITOR position. If the keyswitch is in the RUN/PROGRAM LOAD position, the PLC programming terminal must have the device mode set to Remote RUN-MONITOR or TEST-MONITOR. The STOP qualifier for a PLC-1774 upload function prevents other processes from writing to the device through the DAS. The syntax for the STOP qualifier follows:


UPLOAD dev_name filename /QUALIFIER="STOP" 

When you perform the download function, the keyswitch must be in the RUN-MONITOR, RUN/PROGRAM LOAD, or TEST-MONITOR position. If the keyswitch is in the RUN/PROGRAM LOAD position, the PLC programming terminal must have the device mode set to Remote RUN-MONITOR or Remote TEST-MONITOR. There are two qualifiers associated with the download operation:

The syntax for the STOP and RESTART qualifiers follows:


DOWNLOAD dev_name filename /QUALIFIER="STOP/RESTART" 

Note

You cannot download a PLC-1774 without stopping the device. STOP is a mandatory qualifier.

Table 3-3 displays the modes, qualifiers, and supported functions when you use the download function:

Table 3-3 PLC-1774 Download Function
    After Download
Keyswitch Position Qualifiers Scan Outputs Mode
RUN MONITOR Stop Disable outputs Disable outputs RUN
  Stop/Restart Enable outputs Enable outputs RUN
RUN/PROGRAM LOAD - RUN Stop Disable outputs Disable outputs Remote test
  Stop/Restart Enable outputs Enable outputs Remote run
TEST MONITOR Stop Disable outputs Not modified TEST
  Stop/Restart Enable outputs Not modified TEST
RUN/PROGRAM LOAD - TEST Stop Disable outputs Not modified Remote test
  Stop/Restart Enable outputs Not modified Remote test, remote run

3.2.2.2 PLC-2

You can perform the upload function for the PLC-2 devices in any mode. If you issue the UPLOAD command with the STOP qualifier, the device is issued an upload request. If you are using a 1771-KA interface card and issue the UPLOAD command with the STOP qualifier, the device is issued a download request. The STOP qualifier disables the industrial terminal as well as preventing other processes from writing to the device through the DAS.

Table 3-4 displays the interface, modes, qualifiers, and functions supported, modified, and not supported by the upload function.

Table 3-4 Upload Function
Interface Mode Qualifier Read Write
1771-KA Prog None Not supported Not supported
  Remote prog None Not supported Not supported
  Prog Stop Not supported Not supported
  Remote prog Stop Not supported Not supported
  Run None Supported Supported
  Remote run None Supported Supported
  Test None Supported Supported
  Run test None Supported Supported
  Run Stop Supported Not supported
  Remote run Stop Supported Not supported
  Test Stop Supported Not supported
  Run test Stop Supported Not supported
         
1771-KA2 Prog None Not supported Not supported
  Remote prog None Not supported Not supported
  Prog Stop Not supported Not supported
  Remote prog Stop Not supported Not supported
  Run None Supported Supported
  Remote run None Supported Supported
  Test None Supported Supported
  Run test None Supported Supported
  Run Stop Supported Not supported
  Remote run Stop Supported Not supported
  Test Stop Supported Not supported
  Run test Stop Supported Not supported

Note

Uploading with the STOP qualifier disables the industrial terminal until the upload function is completed.

The action taken for the download function (and associated qualifiers) for a PLC-2 family device depends on the communications interface card being used with the device. Certain revisions of the 1771-KA2 communications adapter do not allow a logic program to be downloaded to the memory of a PLC-2/20 in the RUN/PROG mode.

To determine whether or not the combination of a given revision of the 1771-KA2 interface and PLC-2/20 processor produces this problem, contact an Allen-Bradley representative. Until Allen-Bradley releases a revision of hardware that allows downloading in the RUN/PROG mode, some PLC-2/20s may only be downloaded in the PROG mode.

The 1771-KA interface does not support the SET DATA TABLE SIZE command. The file data table downloaded must have the same data table size as the destination device. If the download function fails with an invalid data table size error, check the history file for the file data table size and reset the device data table size using an industrial terminal. Using the download function through a 1771-KA2 interface sets the device data table size to match the download file data table size.

Valid download functions for the 1771-KA1 and 1771-KA2 interfaces are:

Note

The RUN and RUN/PROG Run mode are not supported through the 1771-KA interface during the download function. The RUN and TEST modes are not supported through the 1771-KA2 interface during the download function. The read and write functions are not supported during a download function on a PLC-2 device.

You must specify the STOP qualifier if the device is to be stopped by the download function. Use the RESTART qualifier to restart the device after the download function is completed.

3.2.2.3 PLC-3

You can perform the upload function for the PLC-3 devices in any mode. The STOP qualifier prevents other processes from writing to the device through the DAS. PLC-3 file allocations are frozen during the upload function regardless of the STOP qualifier.

The controller performs the upload function until the end of the program is reached. Following the upload function, the PLC-3 is returned to its original state.

You can perform the download function for a PLC-3 family device in any mode. If the device is in Run or Test mode, the STOP qualifier is mandatory. If you specify the RESTART qualifier, the device is put in Run mode when the download function completes. If you omit the RESTART qualifier, the device is put in Program mode when the download function completes. The PLC-3's station address is preserved and the station address in the logic file is ignored.

To perform the download function, set the keyswitch to the MEMORY PROTECT OFF position.

3.2.2.4 PLC-5

The upload function can be performed by a PLC-5/XX device in any mode. Upload is not supported for the PLC-5/250.

Specifying /QUALIFIER=STOP helps to prevent modification of device memory during an upload. If you specify the STOP qualifier, the device cannot be scanning during the upload function. If the device is in Remote Run or Remote Test and you specify the STOP qualifier, the device mode is changed to Remote Program until the upload function completes. Note that the PLC-5/15 (Series B, Revision E, or earlier) does not support any read functions except read status during an upload function when you specify the STOP qualifier.

The keyswitch must be in the REMOTE position to use the following qualifiers:

You cannot restart in PROG mode or stop in RUN mode while performing an upload function. The STOP qualifier prevents other processes from writing to the device through the DAS for AB Data Highway Protocol during the upload.

When you perform the download function for a PLC-5 family device, the device can be in any mode except RUN mode. The keyswitch position must be REM or PROG. Note that if the device is in Remote Run or Remote Test mode, the STOP qualifier is mandatory. The RESTART qualifier is only valid if the keyswitch is in the REM position. If you specify the RESTART qualifier, the device is put in the Remote Run mode when the download function completes.

The download function supports the following qualifiers:

You must specify the STOP qualifier if the device is to be stopped by the download function.

Table 3-5 displays the combinations of modes and qualifiers available while performing a download operation. An "N" indicates an invalid combination and a "Y" indicates a valid combination.

Table 3-5 PLC-5 Download Function
  Qualifiers
Mode None Stop Restart Stop/Restart
RUN N N N N
PROG Y Y N N
REM RUN N Y N Y
REM PROG Y Y Y Y
REM TEST N Y N Y

3.2.2.5 SLC

Upload and Download functions are not supported for SLC processors.